Wall systems by fire classification.

16 wall systems in four groups – from non-combustible to acoustic. Classes A2‑s1, d0 and B‑s1, d0 apply to the composite in accordance with DIN EN 13501-1.

Products

Filter products

No products

Reset filters

No product matches this selection. Change the filter or ask us directly.

02Fire classes

What the classes mean.

The right fire classification depends on the area of use, the fire safety concept and the applicable regulations.

How the designation is built

  • A2-s1, d0

    A2
    Non-combustible (national: A2)
    s1
    No or very little smoke
    d0
    No burning droplets
  • B-s1, d0

    B
    Flame-retardant (national: B1)
    s1
    No or very little smoke
    d0
    No burning droplets

Tested as a composite: the classification applies to the board as a composite of surface coating and carrier board, tested to DIN EN 13501-1.

Different fire classes can be combined within one project – for escape routes, public areas, offices or ancillary rooms, for example – while keeping a uniform surface and appearance.

National and European classes compared

Correspondence between national classes to DIN 4102-1 and European classes to DIN EN 13501-1
National class to DIN 4102-1Building authority designationEuropean class to DIN EN 13501-1No smokeNo burning droplets / particles
A1non-combustiblenon-combustibleA1yesyes
A2non-combustiblenon-combustibleA2-s1, d0yesyes
B1flame-retardantflame-retardantB-s1, d0 or C-s1, d0yesyes
B1flame-retardantflame-retardantA2-s2, d0 or A2-s3, d0yes
B1flame-retardantflame-retardantB-s2, d0 or B-s3, d0yes
B1flame-retardantflame-retardantC-s2, d0 or C-s3, d0yes
B1flame-retardantflame-retardantA2-s1, d1 or A2-s1, d2yes
B1flame-retardantflame-retardantB-s1, d1 or B-s1, d2yes
B1flame-retardantflame-retardantC-s1, d1 or C-s1, d2yes
B1flame-retardantflame-retardantA2-s3, d2 / B-s3, d2 / C-s3, d2
B2normally flammablenormally flammableD-s1, d0 or D-s2, d0yes
B2normally flammablenormally flammableD-s3, d0 or Eyes
B2normally flammablenormally flammableD-s1, d1 or D-s2, d1
B2normally flammablenormally flammableD-s3, d1 or D-s1, d2
B2normally flammablenormally flammableD-s2, d2 or D-s3, d2
B2normally flammablenormally flammableE-d2
B3highly flammablehighly flammableF

× = requirement met